Every watt a miner uses becomes heat. A single 3.5 kW miner is a 3.5 kW heater, and ten of them are a furnace. Good cooling keeps chips at safe temperatures, keeps hashrate steady and stretches hardware life.
How much heat?
- 1 W = 3.412 BTU per hour. A 3,500 W miner produces about 11,900 BTU/h.
- 12,000 BTU/h = 1 ton of cooling. One full-size miner is roughly one ton of air conditioning, if you were to cool it with AC.
- Airflow needed (CFM) ≈ BTU/h ÷ (1.08 × temperature rise in °F).
To keep exhaust within 20 °F (about 11 °C) of intake, one 3.5 kW miner needs roughly 550 CFM of fresh air. The miner’s own fans move the air through it; your job is to supply cool air and remove the hot air.
Intake temperature and humidity
- Most air-cooled miners are specified for intake air around 0 to 40 °C. Lower is better for chips and fans.
- Keep humidity non-condensing (typically 10 to 90% relative humidity). Condensation causes corrosion and short circuits.
- Avoid salty or dusty air; filter intakes where you can.
Hot aisle, cold aisle
The golden rule: never let hot exhaust recirculate into the intakes. Line miners up with intakes facing a cool aisle and exhausts facing a hot aisle or a duct that leads outside. Seal gaps so hot air cannot sneak around. In small rooms, a single exhaust duct from each miner to the outside, plus a fresh-air inlet, works well.
Cooling options compared
| Method | Best for | Trade-offs |
|---|---|---|
| Direct air (fans and ducting) | Most sites, cool climates | Dust, noise, depends on outside temperature |
| Evaporative cooling | Hot, dry climates | Adds humidity; needs water and control |
| Air conditioning | Small rooms | Uses a lot of extra power; rarely economic at scale |
| Hydro (liquid cold plates) | Dense or quiet sites, heat reuse | Coolant loop, pumps and dry coolers |
| Immersion | Large engineered sites | Tanks, fluid and maintenance |
Heat and airflow for your fleet
Signs your cooling isn’t enough
- Fans running at 100% all the time.
- Chip or board temperatures near the miner’s limit, or “temperature too high” errors.
- Hashrate dropping in the afternoon or on hot days.
- Room temperature climbing steadily after switching on.
ASIC cooling mistakes to avoid
Recirculating hot air. The most common ASIC cooling problem is exhaust air finding its way back to the intake. Separate the hot and cold sides with a wall, a curtain or ducting, and make sure hot air leaves the room.
Ignoring the incoming air. Intake temperature matters more than room temperature. In summer, a shed or garage can be far hotter than the outside air; measure at the front of the miner.
Forgetting dust and humidity. Filters on the intake keep heatsinks clean but need regular changes. Avoid condensation: cold, humid air on warm boards causes corrosion.
Undersizing the fans. Exhaust fans must move at least as much air as all the miners combined. The power planner estimates the airflow you need. Good ASIC cooling is mostly about moving enough air in the right direction.
Measuring what matters
Place a cheap thermometer and hygrometer at the miner intakes and another at the exhaust. Log the readings for a week across warm and cool hours. The difference tells you whether airflow is enough, and the intake readings show whether your room or shed is drawing in heat from the sun or from recirculated exhaust.
When to upgrade cooling
If miners throttle on warm afternoons, if fan speeds sit near maximum, or if hashrate dips in summer, the cooling has reached its limit. Adding exhaust capacity, better separation of hot and cold air, or moving to hydro or immersion are the usual next steps. Good ASIC cooling pays for itself in steadier hashrate and longer hardware life.
Questions, answered
Can I put a miner in a closet?
Only with a dedicated fresh-air inlet and a ducted exhaust to the outside. A closed closet will overheat quickly.
Is cold weather a problem?
Very cold intake air can cause condensation when it meets warm surfaces. Mix some exhaust air back in winter to keep intake above freezing and humidity non-condensing.